Description
DESCRIPTION CIRCUIT BREAKER NG125N 4P 80A CURVE-C 18658 SCHNEIDER.
Circuit Breaker NG125N 4P 80A Schneider Curve C 18658.
The range of Schneider Electric NG125N 4-pole circuit breakers, with a breaking capacity of 25 kA, suitable for IGA group headers, normally installed in the tertiary or industrial field.
The NG125N allows the coupling of auxiliary elements and Vigi NG125 differential blocks, having to be purchased separately.
We have to take into account that each pole occupies 27 mm of width, especially when calculating the space in the electrical panel. They are mounted on DIN rail and tightened by means of hex keys.
It allows a maximum cable cross-section of 35 mm2 in flexible and up to 50 mm2 in rigid, with a stripped cable depth in terminals of 20 mm.
The tightening torque recommended by the manufacturer is 6 N.m.
C-curve tripping with a maximum operating voltage of 500 V, manually operated.
The dimensions and weight of the automatic are as follows:
– Height: 103 mm.
– Width: 108 mm.
– Depth: 81 mm.
– Weight: 0.96 kg.
Miniature MCB Acti 9, NG125N, 4P, 80A, C-curve, Thermal-magnetic, Rated current (In) 80 A at 40 °C, 0.96 kg. Breaking capacity: 50 kA Icu according to EN/IEC 60947-2, 220…240 V AC 50/60 Hz, 10 kA Icu according to EN/IEC 60947-2, 500 V AC 50/60 Hz, 25 kA Icu according to EN/IEC 60947-2, 380…415 V AC 50/60 Hz, 20 kA Icu according to EN/IEC 60947-2, 440 V AC 50/60 Hz, 20 kA Icu according to EN/IEC 60947-2, <= 500 V DC. Benefits: With the advantages of all the ease of a modular installation, the NG125 circuit breaker combines the performance and robustness required in the most demanding industrial installations. Applications: Protection in all industrial and tertiary buildings: Entrance protection in modular enclosures. Projections in power distribution panels.
Brand: Schneider.
TECHNICAL CHARACTERISTICS
Principal Product range | NG125 | Range | Acti9 | Product name | Acti 9 NG125LMA | Type of product or component | Miniature circuit breaker | Short name of the device | NG125N | Device application | For current> 0.1 A | Number of poles | 4P | Number of protected poles | 4 | [In] Rated current | 80 A at 40 °C | Type of network | Direct current AC | Firing unit technology | Thermal-magnetic | Curve code | C | Cutting capacity | 20 kA Icu at <= 500 V direct current according to Icu 10 kA Icu at 500 V AC 50/60 Hz according to Icu 20 kA Icu at 440 V AC 50/60 Hz according to Icu 25 kA Icu at 380…415 V AC 50/60 Hz according to Icu 50 kA Icu at 220…240 V AC 50/60 Hz in accordance with Icu | Job Category | Category A according to En> 50 A | Sectionalizing power | Yes according to En> 50 A |
Complementary Network frequency | 50/60 Hz | [Ue] Rated operating voltage | 380…415 V AC 50/60 Hz 500 V AC 50/60 Hz <= 500 V direct current 220…240 V AC 50/60 Hz 440 V AC 50/60 Hz | Magnetic bond limit | 8 x pol | [Ics] shear strength in service | 37.5 kA 75 % according to Icu – 220…240 V AC 50/60 Hz 18,75 kA 75 % according to Icu – 380…415 V AC 50/60 Hz 15 kA 75 % according to Icu – 440 V AC 50/60 Hz 7.5 kA 75 % according to Icu – 500 V AC 50/60 Hz 20 kA 100 % according to Icu – <= 500 V direct current | [Ui] Rated insulation voltage | 690 V AC 50/60 Hz in accordance with Icu | [Uimp] Resistance to voltage peaks | 8 kV according to Icu | Contact position indicator | Yes | Type of control | Handle Manual trigger test | On-site signage | Trigger indicator On/off indication | Type of mounting | Adjustable in clip | Mounting bracket | Symmetrical 35 mm DIN rail | Compatibility of distribution block and comb-type busbars | NO | 9 mm steps | 12 | Height | 103 mm | Width | 108 mm | Depth | 81 mm | Product weight | 0.96 kg | Mechanical durability | 20000 cycles | Electrical durability | 5000 cycles | Padlockable | With padlock | Description of locking options | Integrated padlock | Connections – terminals | Tunnel terminals16…70 mm² rigid type Tunnel type terminals10…50 mm² flexible | Stripped cable length for connecting terminals | 20 mm | Tightening torque | 6 N.m | Earth leakage protection | Independent block |
Environment Standards | Icu | IP degree of protection | IP20 according to IEC 60529 | Degree of protection IK | IK05 according to EN/IEC 62263 | Degree of contamination | 3 acorde a En> 50 A | Overvoltage category | IV | Tropicalization | 2 according to IEC 60068-1 | Relative humidity | 95 % at 55 °C | Ambient operating temperature | -30…70 °C | Ambient storage temperature | -40…70 °C |
|
If you need automatics visit our automatics and differentials section.